Friday, December 29, 2023

Automatic Street Light Control Circuit using LDR

 Following is yet another simple Electrical/Electronics project for automatic street light control systems especially for students, newbies and hobbyists.

Features:

  • It is a dark detector circuit based on LDR and a transistor (BC-547 NPN) which automatically switches ON and OFF the street light system.
  • It automatically switches ON street lights when the sunlight goes below the visible region of our eyes. (e.g. in the evening after sunset). 
  • It automatically switches OFF the lights when sunlight falls on it ( i.e. on LDR ) e.g. in the morning, the sensor called LDR (Light Dependent Resistor) senses the light just like our eyes and deactivates the circuit.

Advantages:

  • The automatic operation of street light controlling systems help to reduce the energy consumption as compared to the manually operated street light controlling operations. This is because there is a delay in the earlier switching operations both in morning (during sunrise) and evening (during sunset).
  • On sunny and rainy days, ON and OFF time is noticeably differ which is one of the major disadvantages of using timer circuits or manual operation for switching the street light system.

Components Required:

  • LDR – Light Dependent Resistor
  • 2 Nos. of transistors. (NPN transistor – BC547 or BC147 or BC548)
  • Resistor- 1kΩ, 100kΩ, 330 Ohm & 470 ohms.
  • Light emitting diode (LED) – Any color
  • Connecting wires – (Use single-core plastic-coated wire of 0.6mm diameter (the standard size) or any wire used in computer networking).
  • Power supply-6V or 9V

Procedure

  • Insert first transistor Q1-BC547 (NPN) on breadboard (or general PCB) as shown in the circuit diagram 1.
  • Connect another transistor Q2- BC547 (NPN) on the breadboard as in step 1.
  • Connect  wires across the emitter pin of both transistors and -Ve terminal of battery (lowest/bottom row of breadboard.)
  • Connect  a wire across the Collector pin of transistor Q1 and Base pin of transistor Q2.
  • Connect a resistor 1K across the positive terminal of battery (topmost row of breadboard) and Collector pin of transistor Q1.
  • Connect  Light Dependent Resistor (LDR) across the positive terminal of battery (topmost row of breadboard) and base terminal of transistor Q1.
  • Insert a resistor- 330 Ohm across base pin of transistor Q1 and negative terminal of battery (lowest bottom row of breadboard).
  • Connect a resistor 330R across the positive terminal of battery (topmost row of breadboard) and anode terminal of LED (Light emitting diode) & Connect the cathode terminal of LED to Collector pin of transistor Q2.

The simple circuit is ready for testing now. Connect 6V to 9V battery terminals to the circuit as shown in fig and see the output. As you block light falling on the Light dependent resistor(LDR), the LED glows and vice versa.

LED GLOWS EVEN IN LESS DARKNESS. Use torch light or lighter if the LED glows in less darkness. In addition, you can try to adjust the sensitivity of this circuit by using a variable resistor in place of R1-300 Ohm. You may use other resistances as well, (e.g., 1KΩ, 10KΩ and 100KΩ, etc.)

Pictorial Story: (Click images to enlarge)

Components & Schematic Circuit Diagrams for Automatic Street Light Control System

Automatic-Street-Light-Control-System

Circuit Diagram 1. Automatic Street Light Control System.(Sensor using LDR & Transistor BC 547.). We have tried and Cicuit#1 in this  tutorial but you may also try the second one (Circuit#2) mentioned below ight after circuit no 1.

Automatic Street Light Control Circuit using LDR & Transistor

Circuit Diagram 2 . Automatic Street Light Control System using LDR and two nos. of Transistor BC 547.

Dark Detector Circuit for Automatic Street Light Control using BC547 Transistor and LDR

Automatic-Street-Light-Control-System.-2528Sensor-using-LDR-2526-Transistor-BC-547.-2529-Very-Simple
Automatic Street Light Control System.(Sensor using LDR & Transistor BC 547.) Very Simple.

Automatic Street Light Control System.(Sensor using LDR & Transistor BC 547.) Very Simple.
Automatic Street Light Control System.(Sensor using LDR & Transistor BC 547.) Very Simple.
Automatic Street Light Control System.(Sensor using LDR & Transistor BC 547.) Very Simple.
Whenever light falls on the LDR (Light Dependent resistor), the LED is OFF i.e. the LED does not glow.

Automatic Street Light Control System.(Sensor using LDR & Transistor BC 547.) Very Simple.

In the dark (e.g. when light is blocked to the LDR), the LED is ON i.e. the LED is ON.

Snapshot taken out from the Video.

Automatic Street Light Control System.(Sensor using LDR & Transistor BC 547.) Very Simple.

Some Basic Electronic Projects Circuit Diagrams based on LDR

How to Find the Proper Size of Wire & Cable: Metric & Imperial Systems

 The following step-by-step guide will show you how to find the right size of cable and wire, or any other conductor, for electrical wiring installations with solved examples in both British or English and SI Systems, i.e., Imperial and Metric Systems, respectively.

Keep in mind that selecting the proper wire size is crucial when sizing a wire for electrical installations. An inappropriate size of wire for larger loads with high current may lead to chaos, resulting in the failure of electrical equipment, hazardous fires, and serious injuries.

Factors Affecting the Wire Size

Current Carrying Capacity: The amount of current the wire needs to carry influences its size, ensuring it can handle the load without overheating.

Voltage Drop: For longer distances, consideration of voltage drop becomes crucial to maintain the efficiency and proper functioning of the electrical system.

Ambient Temperature: The environmental temperature affects the wire’s ability to dissipate heat, impacting its current-carrying capacity.

Insulation Type: Different insulating materials have varying thermal and electrical properties, influencing the overall performance and size requirements.

Installation Method: The manner in which the wire is installed, whether in conduit, cable trays, or exposed, can affect its ability to dissipate heat and, consequently, its size.

Conductor Material: Copper and aluminum have different conductivity and temperature characteristics, influencing their suitability for specific applications and, consequently, their sizing.

National Electrical Code (NEC) Guidelines: Adherence to electrical codes and standards is crucial, as they provide specifications and regulations for wire sizing to ensure safety and compliance.

Type of Load: The nature of the electrical load, whether resistive, inductive, or capacitive, can impact the wire size needed for optimal performance.

Cable Bundling: When multiple conductors are bundled together, there is a need to derate the ampacity of each conductor, affecting the overall wire size requirements.

Frequency of Operation: For applications involving alternating current (AC), the frequency of operation can influence the skin effect, affecting the effective resistance and thus impacting wire sizing.

Voltage Drop in a Cables

We know that all conductors, wires and cables (except superconductors) have some amount of resistance.

This resistance is directly proportional to the length and inversely proportional to the diameter of conductor i.e.

R ∝ l/a … [Laws of resistance R = ρ (L/a)]

Whenever current flows through a conductor, a voltage drop occurs. Generally, voltage drop may be neglected for short lengths of conductors. However, in the case of lower diameter and long-length conductors, we must take into account the considerable voltage drops for proper wiring installation and future load management.

According to the NEC – 316-10, add 20% of additional ampacity for every 100 feet of distance (for example between main panel and subpanel) to counter the voltage drop.

According tot the IEEE rule B-23, at any point between power supply terminal and installation, Voltage drop should not increase above 2.5% of the provided (supply) voltage.

How to Find The Suitable Size of Cable & Wire for Electrical Wiring Installation (Solved Examples in British and SI System)

Example:

If the supply voltage is 230V AC, then the value of allowable voltage drop should be;

  • Allowable Voltage Drop = 230 x (2.5/100) = 5.75V

Similarly, if the supply voltage is 120V AC, the allowable voltage drop should be no more than 3V for separate branch circuit (120V x 2.5%) and 5% for feeder and branch circuits (120V x 5%). Refer to the NEC Code – 310-16 which stats 20% of additional ampacity for every 100 feet of distance should be added to counter the voltage drop in the circuit.

In electrical wiring circuits, voltage drops also occur from the distribution board to the different sub circuit and final sub circuits, but for sub circuits and final sub circuits, the value of voltage drop should be half of that allowable voltage drops (i.e. 2.75V of 5.5V as calculated above)

Normally, Voltage drop in tables is described in Ampere per meter (A/m) e.g. what would be the voltage drop in a one meter cable which caries one Ampere current?

There are two methods to define the voltage drop in a cable which we will discus below.

In SI (System international and metric system) voltage drop is described by ampere per meter (A/m).

In FPS (foot pound system) voltage drop is described in length based which is 100 feet.

  • UpdateNow you may also use the following electrical Calculators to find Voltage drop & the wire size in American wire gauge systems.

Tables & Charts for Proper Cable & Wire Sizes

Below are the important tables which you should follow for determining the proper size of cable for Electrical Wiring Installation.

Click image to enlarge

Table-1-current-rating-of-Copper-cables-at-86F-or-30C

Click image to enlarge

Table-Chart-current-rating-of-flexible-cords-Copper-cables-at-86F-30C

How to Find The Suitable Size of Cable & Wire for Electrical Wiring Installation (Solved Examples in British and SI System)

Click image to enlarge

How to Find The Suitable Size of Cable & Wire |Solved Examples steb by step

Table-Cable-Size-Current-Rating-with-voltage-drop-Metric-Decimal-SI-System

How to Find the Voltage Drop in a Cable?

To find voltage drop in a cable, follow the simple steps given below.

  • First of all, find the maximum allowable voltage drop.
  • Now, find the load current.
  • Now, according to the load current, select a proper cable (which current rating should be nearest to the calculated load current) from table 1.
  • From Table 1, find the voltage drop in meter or 100 feet (what system you prefer) according its rated current.

(Stay cool :) We will follow both methods and systems for finding voltage drops (in meters and 100 feet) in our solved example for whole electrical installation wiring).

  • Now, calculate the voltage drop for the actual length of the wiring circuit according to its rated current with the help of following formulas.

(Actual length of circuit x volt drop for 1m) /100 ===> to find Volt drop in per meter.
(Actual length of circuit x volt drop for 100ft) /100 ===> to find volt drop in 100 feet.

  • Now multiply this calculated value of volt drop by load factor where;

Load factor = Load Current to be taken by Cable/ Rated Current of Cable given in the table.

  • This is the value of Volt drop in the cables when load current flows through it.
  • If the calculated value of voltage drop is less than the value calculated in step (1) (Maximum allowable voltage drop), than the size of selected cable is proper
  • If the calculated value of voltage drop is greater than the value calculated in step (1) (Maximum allowable voltage drop), than calculate voltage drop for the next (greater in size) cable and so on until the calculated value of voltage drop became less than the maximum allowable voltage drop calculated in step (1).

How to Determine the Proper Cable & Wire Size for a Given Load?

Below are solved examples demonstrating how to find the proper cable size for a given load.

For a given load, cable size may be determined using various IEC and NEC tables (such Article 310 – Table – 310.15 (B) 16. However, it is crucial to keep in mind the role of ambient temperature and voltage drop for distance between main panel and subpanel.

When determining the size of cable for a given load, take into account the following general rules of thumbs.

  • For a given load, apart from the known current value, there should be a 20% additional margin as safety factor and for future or emergency needs (required by both NEC (220-2) and IEC/IEEE).
  • In the NEC – 316-10, add an additional 20% ampacity to the wire size if the length of the wire exceeds 100 ft (between the main panel and the subpanel).
  • In IEC, the voltage drop should be limited to 1.25%, and for the final sub-circuit, the voltage drop should not exceed 2.5% of the supply voltage from the energy meter to the distribution board.
  • Consider the change in temperature, which affects the ampacity (current carrying capacity) of the wire. When needed, use the temperature factor (Table 3 and related NEC table given at the end of this article).
  • Additionally, take the load factor (diversity factor or demand factor (NEC – 220.42 and (220.45)) into consideration when determining the size of the cable.
  • When calculating the cable size, consider the type of wiring system; for example, in an open wiring system, temperature would be low, but in conduit wiring, temperature increases due to the absence of air.

Solved Examples of Proper Cable & Wire Size

The following examples illustrate how to determine the proper size of cables for electrical wiring installations. These examples will make it easy to understand the method of determining the proper cable size for a given load in both single phase ad three phase wiring installations.

Example 1 – (Imperial Followed by NEC)

What is the right size of wire for a 1,920 W load circuit supplied by 120V AC at 60°C (140°F)?

Solution:

First of all, let’s determine the current in amperes using basic Ohm’s Law that will flow from the 120V breaker to the 1.92kW load.

I (in Amps) = P (in Watts) ÷ V (in Volts)

I = 1,920 W ÷ 120 V

I = 16 Amp

Now, add a safety factor of 1.25, as per NEC Code 220-2 for branch circuits, feeders, and service loads. This code specifies that only 80% of the branch circuit load should be connected to the circuit for the ampacity of the wire for any load. For instance, a 10-ampere breaker should be used for an 8-ampere load point. This way:

I = 16 amp x 1.25

I = 20 Amp.

Now, If you see in the AWG wire size chart and NEC Table 310-15B (16) Article 310.60 (given below), the right size for 20 amp circuit is #12 AWG.

Example 2 – (240V and Distance Involved)

Find the Proper wire size for 2,400 W load circuit supplied by 240V at a distance of 100 feet?

Solution:

Find the current using the following formula (same as mentioned above)

Current = Power ÷ Voltage

I = 2,400 W ÷ 240 V

I = 10 Amperes

Now, multiply the safety factor of 1.25 (80% of load should be connected of the rated ampacity) to the calculated amperage.

I = 10 A x 1.25

I = 12.5 Amperes

As the circuit is 100ft away, add additional 20% ampacity to the calculated value (according to the NEC Code – 310-16) to counter the voltage drop in the circuit.

Total Amps = 12.5A + 2.5A = 15 Amperes.

According to NEC table 310-15B and AWG wire size chart, the suitable wire size for 15 amp circuit is #14 AWG for copper at 60°C (140°F).

Warning: It is always advisable to use copper wire instead of aluminum for better conductivity and reduced power consumption. If it is necessary to use aluminum, the wire size in AWG may differ compared to a copper conductor. Refer to the tables given below to select the wire size accordingly in the case of using aluminum.

In addition, it is recommended to use solid wire instead of stranded wire for a better grip, reduced sparks, and a protected environment from shock and fire.

Example 3 – (Imperial, British or English System)

For an electrical wiring installation in a building, where the total load is 4.5kW and the total length of cable from the energy meter to the sub-circuit distribution board is 35 feet, with a supply voltage of 220V and a temperature of 40°C (104°F), find the most suitable size of cable if wiring is installed in conduits.

Solution:

  • Total Load = 4.5kW = 4.5 x 1000W = 4500W
  • 20% additional load = 4500 x (20/100) = 900W
  • Total Load = 4500W + 900W = 5400W
  • Total Current = I = P ÷ V = 5400W /220V = 24.5A

Now select the size of cable for load current of 24.5A (from Table 1) which is 7/0.036 (28 Amperes). It means we can use 7/0.036 cable according to table 1.

Now, check the selected (7/0.036) cable with the temperature factor in Table 3. The temperature factor is 0.94 (from Table 3) at 40°C (104°F), and the current carrying capacity of (7/0.036) is 28A. Therefore, the current carrying capacity of this cable at 40°C (104°F) would be:

Current rating for 40°C (104°F) = 28 x 0.94 = 26.32 Amp.

Since the calculated value (26.32 Amp) at 40°C (104°F) is less than the current carrying capacity of the (7/0.036) cable, which is 28A, this size of cable (7/0.036) is also suitable with respect to temperature.

Now find the voltage drop for 100 feet for this (7/0.036) cable from Table 4 which is 7V, But in our case, the length of cable is 35 feet. Therefore, the voltage drop for 35 feet cable would be;

Actual Voltage drop for 35 feet = (7 x 35/100) x (24.5/28) = 2.1V

And Allowable voltage drop = (2.5 x 220)/100 = 5.5V

Here, the actual voltage drop (2.1V) is less than the maximum allowable voltage drop of 5.5V. Therefore, the most appropriate and suitable cable size for that given load in the electrical wiring installation is (7/0.036).

Example 4 – (SI / Metric / Decimal System)

What type and size of cable suits for given situation

  • Load = 5.8kW
  • Volts = 230V AV
  • Length of Circuit = 35 meter
  • Temperature = 35°C (95°F)

Solution:

Load = 5.8kW = 5800W

Voltage = 230V

Current = I = P/V = 5800 / 230 = 25.2A

20% additional load current = (20/100) x 5.2A = 5A

Total Load Current = 25.2A + 5A = 30.2A

Now select the size of cable for load current of 30.2A (from Table 1) which is 7/1.04 (31 Amperes). It means we can use 7/0.036 cable according to the table 1.

Now check the selected (7/1.04) cable with temperature factor in Table 3, so the temperature factor is 0.97 (in table 3) at 35°C (95°F) and current carrying capacity of (7/1.04) is 31A, therefore, current carrying capacity of this cable at 40°C (104°F) would be;

Current rating for 35°C (95°F) = 31 x 0.97 = 30 Amp.

Since the calculated value (30 Amp) at 35°C (95°F) is less than that of current carrying capacity of (7/1.04) cable which is 31A, therefore this size of cable (7/1.04) is also suitable with respect to temperature.

Now find the voltage drop for per ampere meter for this (7/1.04) cable from (Table 5) which is 7mV, But in our case, the length of cable is 35 meter. Therefore, the voltage drop for 35 meter cable would be:

Actual Voltage drop for 35meter =

= mV x I x L

= (7/1000) x 30×35 = 7.6V

And Allowable voltage drop = (2.5 x 230)/100 = 5.75V

Here the actual Voltage drop (7.35V) is greater than that of maximum allowable voltage drop of 5.75V. Therefore, this is not a suitable size of cable for that given load. So we will select the next size of selected cable (7/1.04) which is 7/1.35 and find the voltage drop again.

According to Table (5) the current rating of 7/1.35 is 40 Amperes and the voltage drop in per ampere meter is 4.1 mV (See table (5)). Therefore, the actual voltage drop for 35 meter cable would be;

Actual Voltage drop for 35 meter =

= mV x I x L

(4.1/1000) x 40×35 = 7.35V = 5.74V

This drop is less than that of maximum allowable voltage drop. So this is the most appropriate and suitable cable or wire size.

Example 5

Following Loads are connected in a building:-

Sub-Circuit 1

  • 2 lamps each o 1000W and
  • 4 fans each of 80W
  • 2 TV each of 120W

Sub-Circuit 2

  • 6 Lamps each of 80W and
  • 5 sockets each of 100W
  • 4 lamps each of 800W

If supply voltages are 230 V AC, then calculate circuit current and Cable size for each Sub-Circuit?

Solution:

Total load of Sub-Circuit 1

= (2 x 1000) + (4 x 80) + (2×120)

= 2000W + 320W + 240W = 2560W

Current for Sub-Circuit 1 = I = P/V = 2560/230 = 11.1A

Total load of Sub-Circuit 2

= (6 x 80) + (5 x 100) + (4 x 800)

= 480W + 500W + 3200W= 4180W

Current for Sub-Circuit 2 = I = P/V = 4180/230 = 18.1A

Therefore, Cable suggested for sub circuit 1 = 3/.029” (13 Amp) or 1/1.38 mm (13 Amp)

Cable suggested for Sub-Circuit 2 = 7/.029” (21 Amp) or 7/0.85 mm (24 Amp)

Total Current drawn by both Sub-Circuits = 11.1A + 18.1A = 29.27 A

So cable suggested for Main-Circuit = 7/.044″ (34 Amp) or 7/1.04 mm (31 Amp)

Example 6

A 10H.P (7.46kW) three phase squirrel cage induction motor of continuous rating using Star-Delta starting is connected through 400V supply by three single core PVC cables run in conduit from 250feet (76.2m) away from multi-way distribution fuse board. Its full load current is 19A. Average summer temperature in Electrical installation wiring is 35°C (95°F). Calculate the size of the cable for the motor?

Solution:

  • Motor load = 10H.P = 10 x 746 = 7460W *(1H.P = 746W)
  • Supply Voltage = 400V (3-Phase)
  • Length of cable = 250feet (76.2m)
  • Motor full load Current = 19A
  • Temperature factor for 35°C (95°F) = 0.97 (From Table 3)

Now select the size of cable for full load motor current of 19A (from Table 4) which is 7/0.36” (23 Amperes) *(Remember that this is a 3-phase system i.e. 3-core cable) and the voltage drop is 5.3V for 100 Feet. It means we can use 7/0.036 cable according Table (4).

Now check the selected (7/0.036) cable with temperature factor in table (3), so the temperature factor is 0.97 (in table 3) at 35°C (95°F) and current carrying capacity of (7/0.036”) is 23 Amperes, therefore, current carrying capacity of this cable at 40°C (104°F) would be:

Current rating for 40°C (104°F) = 23 x 0.97 = 22.31 Amp.

Since the calculated value (22.31 Amp) at 35°C (95°F) is less than that of current carrying capacity of (7/0.036) cable which is 23A, therefore this size of cable (7/0.036) is also suitable with respect to temperature.

Load factor = 19/23 = 0.826

Now find the voltage drop for 100feet for this (7/0.036) cable from table (4) which is 5.3V, But in our case, the length of cable is 250 feet. Therefore, the voltage drop for 250 feet cable would be;

Actual Voltage drop for 250feet = (5.3 x 250/100) x 0.826 = 10.94V

And maximum Allowable voltage drop = (2.5/100) x 400V= 10V

Here the actual Voltage drop (10.94V) is greater than that of maximum allowable voltage drop of 10V. Therefore, this is a not a suitable size of cable for the given load. So we will select the next size of selected cable (7/0.036) which is 7/0.044 and find the voltage drop again. According to Table (4) the current rating of 7/0.044 is 28 Amperes and the volt drop in per 100 feet is 4.1V (see Table 4). Therefore, the actual voltage drop for 250 feet cable would be;

Actual Voltage drop for 250 feet =

Volt drop per 100 feet x length of cable x load factor

= (4.1/100) x 250 x 0.826 = 8.46V

And Maximum Allowable voltage drop = (2.5/100) x 400V= 10V

The actual voltage drop is less than that of maximum allowable voltage drop. So this is the most appropriate and suitable cable size for electrical wiring installation in a given situation.

NEC Wire Size Table 310.15(B)(16) (formerly Table 310.16) & Chart

NEC (National Electrical Code) Table 310.15(B)(16) (formerly Table 310.16) – 310.60 – ARTICLE 310 – Conductors for General Wiring & Allowable Ampacities of Conductors & Wire Sizes based on AWG (American Wire Gauge).

310.60               ARTICLE 310 — CONDUCTORS FOR GENERAL WIRING
Table 310.15(B)(16) (formerly Table 310.16) Allowable Ampacities of Insulated Conductors Rated Up to and Including 2000 Volts, 60°C Through 90°C (140°F Through 194°F), Not More Than Three Current-Carrying Conductors in Raceway, Cable, or Earth (Directly Buried), Based on Ambient Temperature of 30°C (86°F)*
Size AWG or kcmilTemperature Rating of Conductor [See Table 310.104(A).]Size AWG or kcmil
60°C (140°F)75°C (167°F)90°C (194°F)60°C (140°F)75°C (167°F)90°C (194°F)
Types TW, UFTypes RHW, THHW, THW, THWN, XHHW, USE, ZWTypes TBS, SA, SIS, FEP, FEPB, MI, RHH, RHW-2, THHN, THHW,

THW-2, THWN-2, USE-2, XHH, XHHW,

XHHW-2, ZW-2

Types TW, UFTypes RHW, THHW, THW, THWN, XHHW, USETypes TBS, SA, SIS, THHN, THHW,

THW-2, THWN-2, RHH, RHW-2, USE-2, XHH, XHHW, XHHW-2, ZW-2

COPPERALUMINUM OR COPPER-CLAD ALUMINUM
18**14
16**18
14**152025
12**20253015202512**
10**30354025303510**
84050553540458
65565754050556
47085955565754
3851001156575853
29511513075901002
1110130145851001151
1/01251501701001201351/0
2/01451751951151351502/0
3/01652002251301551753/0
4/01952302601501802054/0
250215255290170205230250
300240285320195230260300
350260310350210250280350
400280335380225270305400
500320380430260310350500
600350420475285340385600
700385460520315375425700
750400475535320385435750
800410490555330395445800
900435520585355425480900
10004555456153754455001000
12504955906654054855451250
15005256257054355205851500
17505456507354555456151750
20005556657504705606302000
  •    *Refer to 310.15(B)(2) for the ampacity correction factors where the ambient temperature is other than 30°C (86°F). Refer to 310.15(B)(3)(a) for more than three current-carrying conductors.
  •    **Refer to 240.4(D) for conductor overcurrent protection limitations.

Here is the NEC table as a chart (image format to downloads as a reference)

Click image or open in a new tab to enlarge

NEC Table 310.15(B)(16) (formerly Table 310.16) - 310.60 - ARTICLE 310 - CONDUCTORS FOR GENERAL WIRING & Allowable Ampacities of Conductors & Wire Sizes
NEC Table 310.15(B)(16) (formerly Table 310.16)
Wire Gauge Size & Wire Ampacity Table
AWG Wire Size Chart